CyberPower-2U Switched ATS 32Amp input/output - (PDU32SWHVCEE18ATNET) - SNMP Network Connection - 16x IEC C13 & 2x IEC C19 out - IEC 309-32A in - 2 Years WTY

  • SKU: CP89178
  • Manufacturer P/N: PDU32SWHVCEE18ATNET
  • Availability: In Stock
  • SKU: CP89178
  • State(s) NSW
    Unit(s) 1
Availability: In Stock
State(s) NSW
Unit(s) 1

GENERAL
Type: Switched
Phase: Single Phase
INPUT
Nominal Input voltage (Vac): 200 ~ 240
Input Frequency (Hz): 50/60
Maximum Input Current (A): 32
Input Connector Type: IEC 60309 32A x 2
Power Cord Length (ft.): 10
Power Cord Length (m.): 3.05
OUTPUT
Output Voltage (V): Depends on Input
Overload Protection: Circuit Breaker
Over Current Protection (Each Bank) (A): 20
Outlet(s) - # of Bank(s) (Bank): 2
Outlet(s) – Total: 18
Outlet(s) – Front: 18
Outlet Type: IEC C19 x 2/IEC C13 x 16
Remote Individual Outlet Control: Yes
PHYSICAL
Installed Rack Height (U): 2
Form Factor: 2U Horizontal Rackmount
Enclosure Construction: Steel
Color: Black
Cord Retention Tray: Yes
IEC Receptacle Locking: Yes
External Site Ground Pin: Yes
Adjustable Mounting Brackets: 1 set
PHYSICAL SIZE
Dimensions (WxHxD) (in.): 17.05 x 3.5 x 9.3
Unit Dimensions (WxHxD) (mm): 433 x 88 x 236
Net Weight (Ibs.): 18.3
Net Weight (kg): 8.3

Specification

General Information

Manufacturer
CyberPower Systems, Inc
Manufacturer Part Number
PDU32SWHVCEE18ATNET
Manufacturer Website Address
http://www.cyberpower.com/au
Brand Name
CyberPower
Product Model
PDU32SWHVCEE18ATNET
Product Name
PDU32SWHVCEE18ATNET 18-Outlet PDU
Marketing Information

CyberPower Automatic Transfer Switches equipped with dual input sources provide reliable redundant power to single-corded network devices.

The units automatically transfer power from selected source to the other power source to maintain continuous output without interruption. This will ensure the highest level of protection to equipment that does not have redundant power supply.

Configurable threshold for input voltage and device load allows extensive application scenarios. With a front digital multifunction LCD readout for real-time power monitoring and local management, you can conveniently monitor and configure the load to avoid overloads and efficiently balance load levels.

Via the SNMP/HTTP protocol through Web, SNMP, and Telnet, the ATS are able to switch outlets off and on to reboot connected equipment remotely.

Product Type
PDU

Technical Information

Input Receptacles
2 x IEC 60309 32A
Output Receptacles
16 x IEC 60320 C13
2 x IEC 60320 C19
Overload Protection
Overcurrent Protection

Power Description

Input Voltage
230 V AC
Input Voltage Range
200 V AC - 240 V AC
Output Voltage
230 V AC
Input Current
32 A

Management

Management

Protocols:

  • TCP/IP
  • UDP
  • DHCP
  • SNMP v1/v3
  • HTTP(s)
  • Telnet
  • SSH
  • SSL
  • NTP
  • SMTP
  • IPv4
  • IPv6

Interfaces/Ports

Network (RJ-45)
Yes

Physical Characteristics

Mounting Orientation
Horizontal
Mount Type
Rack-mountable
Rack Height
2U
Height
88.9 mm
Width
433.1 mm
Depth
236.2 mm
Weight (Approximate)
8.30 kg

Miscellaneous

Environmentally Friendly
Yes